Diesel generator set start-up requirements
1. When the indoor air temperature is lower than 20℃, the Deutz diesel generator will turn on the electric heater to preheat the machine.
2. Check the machine body and its surroundings to see if there is any debris that hinders the operation. If there is any, it should be removed in time.
3. Check crankcase oil level, fuel tank oil level, radiator water level. If the oil level is lower than the specified value, it should be replenished to the normal position.
4. Check that the fuel supply valve and cooling water shut-off valve are in the open position.
5. Check whether the voltage of the battery pack of the starter is normal.
6. Check the test button of the power distribution panel and observe whether each alarm indicator light is turned on.
7. Check whether the switches of the power distribution panel are in the off position, and whether the indicators of each instrument are in the zero position.
8. Start the intake and exhaust fans.
9. Press the start button of the engine to start it running. If the first start fails, you can press the corresponding reset button on the power distribution panel, and wait for the alarm to clear and the unit to return to normal before starting the second time. After starting, the sound of the machine running is normal, the running indicator of the cooling water pump is on and the road meter indicates normal, and the startup is successful.